Description détaillée:
-
Highly Integrated All-in-One Design: Combines Processeur, alimentation, and input/output units into a single compact module, allowing the construction of a basic control system without additional power or I/O expansion modules, greatly simplifying system configuration and installation.
-
Flexible Relay Outputs: All 10 output points are relay contact type, each independently isolated, capable of flexibly driving either AC or DC loads (such as contactor coils, électrovannes, indicator lights) with a load capacity of 2A @ 250V AC / 2A @ 30V DC, providing direct driving capability for small loads.
-
Reliable Digital Inputs: Le 14 input points are compatible with DC 24V signals and employ a sinking (Sink) méthode de saisie, allowing connection to common field devices like pushbuttons, commutateurs, and proximity sensors. Input/output terminals use removable screw-clamp terminal blocks for convenient wiring.
-
Easy Programming and Maintenance: Programmed using Mitsubishi’s simple programming software (par ex., ALPHA2 Programming Tool) via a dedicated programming cable. The instruction set is simple to learn. Intégré RUN/STOP switch et status LEDs (POWER, RUN, ERROR, I/O status) facilitate operation and troubleshooting.
-
Built-in Rich Functions: Despite being a micro PLC, it includes basic logic elements such as timers, compteurs, auxiliary relays, et un high-speed counter function (on some input points), meeting the needs of most simple sequential control and counting applications.
-
Cost-Effective: As an entry-level PLC product, it offers highly competitive pricing while maintaining Mitsubishi’s reliability, making it an ideal choice for cost-sensitive small projects.
Spécifications clés:
| Paramètre | Détails |
| Modèle | AL2-24MR-D |
| Série | ALPHA2 (AL2) Series Micro PLC |
| Alimentation | DC 24V |
| Number of Inputs | 14 points |
| Input Type | DC 24V, Sinking (Sink) Input |
| Number of Outputs | 10 points |
| Type de sortie | Relay Output (Independent Contacts) |
| Output Contact Rating | 2 A @ 250V AC / 2 A @ 30V DC (Resistive Load) |
| Program Capacity | Environ. 500 steps (typical) |
| Number of Instructions | Environ. 30 basic instructions |
| Built-in High-Speed Counter | 1 point (Single-phase 5 kHz) |
| Communication/Programming Port | Dedicated Programming Port (requires AL2-CNV/AL2-C05V cable) |
| Température de fonctionnement | -10 ~ 55 °C |
| Classe de protection | IP20 (Open Type, requires enclosure mounting) |
| Montage | 35mm DIN Rail Mount or Screw Mount |